Chloride® FP50R DC UPS

Designed to provide a simple, fast and cost effective solution for DC power requirements.

Enquire

TypeDC UPS /
Natural cooling

Ratings24...125 Vdc |
10...250 A

TechnologySCR

Chloride® FP50R DC UPS

Designed to provide a simple, fast and cost effective solution for DC power requirements.

Enquire

TypeDC UPS /
Natural cooling

Ratings24...125 Vdc |
10...250 A

TechnologySCR

Market & Industry Type

  • Power Transmission and Distribution (Motorised circuit breakers, control rooms, SCADA, automatic controllers)

  • Energy Production (Safety systems, SCADA, automatic controllers)

  • Process Industries (Control systems, SCADA, automatic controllers)

Key Advantages

More reliable

Thanks to the proven thyristor technology that Chloride® has mastered for over 70 years.

More robust

With a natural cooling design throughout the range. No risk of fan-related failures.

Less maintenance

Due to the use of long-life components.

Easier to use

With its human-machine interface featuring a large, high-contrast display. The display shows the rectifier diagram and indicates any faults, which are also indicated by summary LEDs.

Faster availability

Thanks to its design in 100% industrialised configurable sub-assemblies. The Chloride® FP50R charger-rectifier can be available in only 6 to 8 weeks.

Range

1-Phase

10/25/40/60/100 Adc

3-Phase

25/40/60/100/160/250 Adc

Input

Rated voltage

1-Phase: 230Vac (220,240)

3-Phase: 400Vac (380,415) / 208Vac

Input voltage tolerance

± 10%

Frequency

47Hz / 63Hz

 

Frequency tolerance

± 5%

Inrush current

1-Ph: < 15 ln

3-Ph: < 10 ln

Output

Rated voltage DC

24V (17V-34V), 48V (34V-68V), 110-125V (88V-179V)

Voltage stability (in stabilised floating mode, input within tolerances)

Single system: ± 1%

 

Dual system: ± 1% to ± 2%

Voltage ripple rate

≤ 5 % at 100 % load

Battery

Type

Lead-Acid or Nickel-Cadmium, VLA or VRLA

Autonomy

From a few minutes to several hours, on request

24V - Number of battery cells

Lead-Acid: 12

NiCd: 18 - 20

48V - Number of battery cells

Lead-Acid: 24

NiCd: 36 - 44

110V - Number of battery cells

Lead-Acid: 54

NiCd: 82 - 92

125V - Number of battery cells

Lead-Acid: 60

NiCd: 91- 105

General Data

Operating temperature

0 to 40°C (2)

Storage temperature range

-20 to 70°C (excluding battery)

Relative humidity

< 95% non-condensing at 20°C

Altitude

1000m (2) (without downgrading the system)

Rectifier technology

SCR, 2-pulses thyristors

Cooling

Natural convection

External protection class

IP21 to IEC 60529 (other protection classes available: IP41 / IP42)

Internal protection

Protection against unintentional direct contact according to IEC 62477-1

Cable entry

Cable entry

Cabinet colours

Grey RAL 7035 / Grey RAL 7032

Dimensions

Varies according to size and options

Monitoring

Local, on the front panel

Graphic display with navigation buttons (75mm x 45mm)

List of relay alarms

Standards: general alarm, mains failure, battery charging, end of discharge Options: ground fault, boost mode, overvoltage, undervoltage

Alarm relays, contact characteristics

Changeover contact, switching capacity in accordance with DIN VDE 0660/IEC 60947: 1 A (24 V (DC13)), 0.2 A (110 V, DC13), 0.1 A (220 V, DC13) 3 A (24 V, AC15), 3 A (120 V, AC15), 3 A (230 V, AC15)

Remote control (optional)

RS485, TCP-IP, IEC 61850, SNMP, PROFIBUS

Standards

IEC 61000-6-2 : 2016

Electromagnetic compatibility (EMC) - Part 6-2: General requirements - Emission for industrial environments.

IEC 61000-6-4 : 2018

Electromagnetic compatibility (EMC) - Part 6-4: Generic standards - Emission for industrial environments.

IEC 61000-6-5 : 2015

Electromagnetic compatibility (EMC) - Part 6-5: Generic standards - Emission for equipment used in power plant and substation environments.

IEC 62477-1 : 2022

Safety requirements for electronic power conversion systems and equipment - Part 1: General.

IEC 60146-1-1 : 2009

Semiconductor converters - General requirements and mains switched converters - Part 1-1: Specification of basic requirements.

IEC 60529 : 2013

Degrees of protection provided by the enclosures (IP Code).