Chloride® CP70R DC UPS

CP as Customized Product. The most advanced product in terms of possibilities. A natural cooled product.

Enquire

UPS TypeDC UPS /
Natural cooling

Ratings24...220 Vdc |
25...2000A

TechnologySCR

Chloride® CP70R DC UPS

CP as Customized Product. The most advanced product in terms of possibilities. A natural cooled product.

Enquire

UPS TypeDC UPS /
Natural cooling

Ratings24...220 Vdc |
25...2000A

TechnologySCR

Market & Industry Type

  • Power generation plants

  • Transmission and Distribution substations

  • Continuous process industries

  • Oil & Gas and Petrochemical industries

  • Rail transport

Key advantages

User friendly

Large color touch screen with 2000-event exportable log.

One of the best on the Industrial UPS Market.

USB access

Export of all the recorded events using USB flash drive.

Memorization of complete electronic settings for future maintenance needs.

Batteries compatibility

Innovative full integration with SMC/Salt Batteries (Sodium Metal Chloride Batteries).

Full compatibility with Lead-acid, nickel-cadmium batteries, sealed or vented and Lithium-Ion.

Life time

Designed for 20+ years of continuous operation with appropriate maintenance plan.

Inrush current

Reduced ≤ 10xIn to avoid oversizing upstream protection and 2-step strat-up.

Input

AC voltage

Single phase 1 x 230 V (220, 240)

Three phase

3 x 400 V (380, 415)

Voltage tolerance

+/- 10 %

Neutral configuration

Any configuration, with or without neutral

Frequency

50 Hz (60 Hz)

Frequency tolerance

+/- 5 %

Frequency range (temporary)

45 Hz to 65 Hz (with 50 Hz nominal)

Total harmonic current distorsion (THDI)

< 34 % (6-pulse version)< 34 % (6-pulse version)

Inrush current

< 15 x In (for 6-pulse and 12-pulse)

Output

Nominal DC voltage

24...400V

Output DC voltage range

17...550 V

Voltage stability (in stabilized floating mode, input within tolerance)

Unitary system +/-1 %

Parallel systems

+/-1 % to +/-2 %

Voltage ripple

≤ 1 % RMS, in float mode, battery disconnected

Current limitation

I nominal

Battery

Type

Salt Metal Chloride, Lead acid or nickel cadmium, vented or recombination

Autonomy

From few minutes to several hours, on request

Battery current limitation (typical, float, & boost modes)

0.1 C (lead-acid battery) / 0.2 C (nickel-cadmium battery)

General data

Operating temperature

0 to 40 °C (-20°...55°C on request)

Storage temperature

-20 to +70 °C

Relative humidity

< 95 % non condensing

Operating altitude

1000 m max without derating

Cooling

Natural convection on most of the range

Efficiency

Up to 96 % according to rating

External protection

IP 20 according to IEC 60529

Internal protection

Protection against unintentional direct contacts, as per IEC 60950-1

Noise (at 1m in front of the unit)

55 – 65 dB according to rating

Cabinet color

Grey RAL 7032

Dimensions

Varying according to ratings & options

Ratings

1 phase input

24 Vdc ... 127 Vdc

2 phase input

25...250 Vdc

3 phase input

24 Vdc...400Vdc

3 phase output

25 A ... 2500 A