XP20R DC UPS - ATEX/IECEx
Chloride® XP20R is an industrial rectifier / battery charger explosion proof Zone 1 & 2 developed specifically for offshore environment & tough operating conditions. It is the smallest DC UPS of XP range.
UPS TypeDC UPS ATEX/IECEx
Rating <1800W
TechnologySMR
XP20R DC UPS - ATEX/IECEx
Chloride® XP20R is an industrial rectifier / battery charger explosion proof Zone 1 & 2 developed specifically for offshore environment & tough operating conditions. It is the smallest DC UPS of XP range.
UPS TypeDC UPS ATEX/IECEx
Rating <1800W
TechnologySMR
Market & Industry Type
Offshore production process in Explosion-risk areas
Wellhead platforms / Unmanned platforms
Pipelines instrumentation
Refineries
Downloads
Features & Benefits
Read lessKey features
Small footprint
To optimize space on offshore platform.
Durability
Optimized thermal management.
Immunity
Strong immunity to perturbations.
Safe control, door closed
Allows the user to operate the switches, circuit breakers, and control buttons door closed.
Smart access to data
Large graphical user interface on the front.
Safe and easy maintenance
Once open, the front door gives direct access to all components.
Alarms
Embedded event logger (up to 2000 events).
Close range Wi-Fi module - To download the event logger without opening the equipment enclosure.
Technical Specification
Read lessInput
AC Voltage
1 x 230 V (220, 240)
Voltage tolerance
+15% / -18% (187 V to 264 V)
Frequency
50 Hz (60 Hz)
Frequency range
From 47 Hz to 63 Hz
Total harmonic current distortion (THDi)
≤ 5%
Inrush current
≤ 10 x In
Input power factor
≤0.95
Output
Nominal DC Voltage
24 V / 48 V
Output DC voltage range
+/-15 %
Static regulation
+/-1 %
Voltage ripple
≤ 0.1 % RMS (disconnected battery)
Current limitation
I nominal
Charging mode
With valve regulated lead acid: single charge mode
With recombination nickel cadminum: single charge mode (recommended) or dual charge mode
Charging current
With valve regulated lead acid : 0.05C10 to 0.1C
With recombination nickel cadmium: 0.1C
(up to 0.2C subject to battery enclosure certification limits)
Protections
Input
Type : MCCB
Breaking capacity : 18 kA
Lightning arrestor / spike suppressor
Battery
Pre-heating start-up
Type : MCCB
Breaking capacity : 18 kA
Battery reverse polarity protection
Low Voltage Disconnection (LVD) device
External battery cut-off
Output
Type : MCCB
Breaking capacity : 18 kA
Isolation Voltage
Input / output: 4200 Vdc / 1 min
Input / ground: 2300 Vdc / 1 min
Output / ground: 1500 Vdc / 1 min
System
Internal anti-condensation paint
Conformal coating of Printed Circuit Boards (PCB)
Volatile Corrosion Inhibitot (VCI) for 2 years
Battery
Type
Valve regulated lead acid
Autonomy
From few minutes to several hours, upon requirement
Ratings
Output voltage
24 Vdc 48 Vdc
Output current
24 Vdc ==> 15, 25 , 50A 48 Vdc ==> 15, 25 A
General Data
Execution
II 2 G Ex db eb IIB+H2 T5 Gb IP66
External ingress pprotection
IP 66
Rectifier efficiency
From 86 % (24 V) to 89 % (48 V)
Operating temperature
From 0 °C to 50 °C (external temperature, without derating)
Storage temperature
From -20 °C to +70 °C (battery excluded)
Relative Humidity
100 %, condensing
Operating Altitude
1000 m (without system derating)
Cooling
Natural convection
Noise
≤ 30 dB (at 1m in front of the unit)
Dimensions
W: 490 mm / D: 491 mm / H: 1200 mm
Weight
Varying according to ratings and options
Installation
Vertically wall-mounted
Design life
20 years
Materials
Charger enclosure: Ex d, copper-free marine grade aluminum
Customer terminal box: Ex e, stainless steel 316L
Supporting frame: C35 steel
Painting
External: C5 marine-grade painting, RAL 7035 or 7032Internal: Hygroscopic orange RAL 2004
Customer connection
Through pre-dilled gland plate, 1.5mm thickness
Standards
Standards
IEC EN 60146-1-1:2009
IEC EN 61000-6-2:2006
IEC EN 61000-6-4:2007 AMD1:2011
IEC EN 61439-1:2011
IEC EN 60529:1989 AMD1:1999
NFC 58-311:1990
IEC EN 60079-0
IEC EN 60079-1
IEC EN 60079-7