XP20R DC UPS - ATEX/IECEx

Chloride® XP20R is an industrial rectifier / battery charger explosion proof Zone 1 & 2 developed specifically for offshore environment & tough operating conditions. It is the smallest DC UPS of XP range.

Enquire

UPS TypeDC UPS ATEX/IECEx

Rating <1800W

TechnologySMR

XP20R DC UPS - ATEX/IECEx

Chloride® XP20R is an industrial rectifier / battery charger explosion proof Zone 1 & 2 developed specifically for offshore environment & tough operating conditions. It is the smallest DC UPS of XP range.

Enquire

UPS TypeDC UPS ATEX/IECEx

Rating <1800W

TechnologySMR

Market & Industry Type

  • Offshore production process in Explosion-risk areas

  • Wellhead platforms / Unmanned platforms

  • Pipelines instrumentation

  • Refineries

Key features

Small footprint

To optimize space on offshore platform.

Durability

Optimized thermal management.

Immunity

Strong immunity to perturbations.

Safe control, door closed

Allows the user to operate the switches, circuit breakers, and control buttons door closed.

Smart access to data

Large graphical user interface on the front.

Safe and easy maintenance

Once open, the front door gives direct access to all components.

Alarms

Embedded event logger (up to 2000 events).

Close range Wi-Fi module - To download the event logger without opening the equipment enclosure.

Input

AC Voltage

1 x 230 V (220, 240)

Voltage tolerance

+15% / -18% (187 V to 264 V)

Frequency

50 Hz (60 Hz)

Frequency range

From 47 Hz to 63 Hz

Total harmonic current distortion (THDi)

≤ 5%

Inrush current

≤ 10 x In

Input power factor

≤0.95

Output

Nominal DC Voltage

24 V / 48 V

Output DC voltage range

+/-15 %

Static regulation

+/-1 %

Voltage ripple

≤ 0.1 % RMS (disconnected battery)

Current limitation

I nominal

Charging mode

With valve regulated lead acid: single charge mode

With recombination nickel cadminum: single charge mode (recommended) or dual charge mode

Charging current

With valve regulated lead acid : 0.05C10 to 0.1C

With recombination nickel cadmium: 0.1C

(up to 0.2C subject to battery enclosure certification limits)

Protections

Input

Type : MCCB

Breaking capacity : 18 kA

Lightning arrestor / spike suppressor

Battery

Pre-heating start-up

Type : MCCB

Breaking capacity : 18 kA

Battery reverse polarity protection

Low Voltage Disconnection (LVD) device

External battery cut-off

Output

Type : MCCB

Breaking capacity : 18 kA

Isolation Voltage

Input / output: 4200 Vdc / 1 min

Input / ground: 2300 Vdc / 1 min

Output / ground: 1500 Vdc / 1 min

System

Internal anti-condensation paint

Conformal coating of Printed Circuit Boards (PCB)

Volatile Corrosion Inhibitot (VCI) for 2 years

Battery

Type

Valve regulated lead acid

Autonomy

From few minutes to several hours, upon requirement

Ratings

Output voltage

24 Vdc 48 Vdc

Output current

24 Vdc ==> 15, 25 , 50A 48 Vdc ==> 15, 25 A

General Data

Execution

II 2 G Ex db eb IIB+H2 T5 Gb IP66

External ingress pprotection

IP 66

Rectifier efficiency

From 86 % (24 V) to 89 % (48 V)

Operating temperature

From 0 °C to 50 °C (external temperature, without derating)

Storage temperature

From -20 °C to +70 °C (battery excluded)

Relative Humidity

100 %, condensing

Operating Altitude

1000 m (without system derating)

Cooling

Natural convection

Noise

≤ 30 dB (at 1m in front of the unit)

Dimensions

W: 490 mm / D: 491 mm / H: 1200 mm

Weight

Varying according to ratings and options

Installation

Vertically wall-mounted

Design life

20 years

Materials

Charger enclosure: Ex d, copper-free marine grade aluminum

Customer terminal box: Ex e, stainless steel 316L

Supporting frame: C35 steel

Painting

External: C5 marine-grade painting, RAL 7035 or 7032Internal: Hygroscopic orange RAL 2004

Customer connection

Through pre-dilled gland plate, 1.5mm thickness

Standards

Standards

IEC EN 60146-1-1:2009

IEC EN 61000-6-2:2006

IEC EN 61000-6-4:2007 AMD1:2011

IEC EN 61439-1:2011

IEC EN 60529:1989 AMD1:1999

NFC 58-311:1990

IEC EN 60079-0

IEC EN 60079-1

IEC EN 60079-7