Chloride® FP40R DC UPS

Designed to provide a simple, fast and cost effective solution for DC power requirements.

Enquire

TypeDC UPS /
Natural cooling

Ratings24...220 Vdc |
25...400 A

TechnologySCR

Chloride® FP40R DC UPS

Designed to provide a simple, fast and cost effective solution for DC power requirements.

Enquire

TypeDC UPS /
Natural cooling

Ratings24...220 Vdc |
25...400 A

TechnologySCR

Market & Industry Type

  • Power transmission and distribution

  • Continuous process industries

  • Petrochemical and chemical industries

  • Water and wastewater industries

Key Advantages

Improved reliability

Provided by a fully controlled SCR bridge and a reduced quantity of components.

Adaptability

Thanks to a selection of industrialized options and an easy parameter settings for quick onsite adjustments.

Simplicity

Of the product design to improve MTBF and to reduce MTTR.

Low Voltage Ripple

To optimize battery life.

Low inrush current

< 8In not to oversize mains power supply (3-phase).

Compact design

With the capability to integrate the battery in the charger cabinet.

Human-Machine Interface (HMI)

To deliver appropriate information level to the user.

Ingress protection

Up to IP55 for harsh environmental conditions.

Compatibility

With nickel-cadmium and lead-acid batteries, vented or gas-recombination types.

Galvanic isolation

Between input and output.

Digital control

Digital control and monitoring.

Wide choice

Wide choice of configurations and options.

Input

Model

1-Ph: FP40R10

3-Ph: FP40R30

Input voltage (other voltage on request)

1-Ph: 230 VAC ± 10%

3-Ph: 400 VAC ± 10%

Inrush current

1-Ph: < 15 ln

3-Ph: < 8 ln

Frequency range

 

From 47 to 63 Hz

Output

Available rating

See ratings table

Nominal DC voltage

24/48/110/220V

Static regulation

1 %

Voltage ripple 1-ph

Disconnected battery (< 2.5 %)

Voltage ripple 3-ph

Disconnected battery (< 0.7 %)

Supervision

Charger status

Charger status and alarms on displaying Unit

Displayed values

Output voltage, output current, battery Current

Remote signaling

With 4 dry contacts

Event log

Up to 100 events

Battery

Type

Lead acid or nickel cadmium, vented or recombination

Autonomy

From few minutes to several hours, as required

General Data

Rectifier efficiency

From 83 % to 94 % (according to model)

Operating temperature

From 0 to 40 °C (without system derating)

Storage temperature

From -20 °C to +70 °C (battery excluded)

Relative humidity

< 95 % non condensing at 20 °C

Operating altitude

1000 m (without system derating)

Cooling

Natural or fan-assisted (according to rating)

External ingress protection

IP20

Internal protection

Internal protection

Noise (at 1m in front of the unit)

≤ 60 dB

Isolation

Input - Output 2500 VAC / 1 minute

Frame colour

RAL 7035 or RAL 7032

Dimensions

Varying according to ratings and options (consult us)

Output current (A) vs Output voltage (Vdc)

Ratings with 1-phase input

24 Vdc: 100A

48 Vdc: 40/60/100A

110-125 Vdc : 25/40/60/100A

220 Vdc: 25A

Ratings with 3-phase input

24 Vdc: 35/65/100/160/220/300/400A

48 Vdc: 35/65/100/160/220/220/300/400A

110-125 Vdc: 35/65/100/160/220/300/400A

220 Vdc: 35/65/100/160/220/300A

Options

Charger

Input circuit breaker or molded case circuit breaker (16 kA or 36 kA)

Position contact on AC input circuit breaker

Paralleling diode

Dropping diode

DC earth fault monitor

Customer connection on terminal blocks

Ultra low voltage ripple < 0.1 % (48 V)

Measurements of AC input voltage, current and frequency

Battery

Battery protection (fuses or circuit breaker with contact)

Protection against battery reversed polarity

Battery Low Voltage Disconnection (LVD)

Battery Low Voltage Disconnection (LVD) Temperature sensor for battery charge compensation

Test battery presence or test battery capacity

Mechanical

Operating temperature up to 55 °C (with system derating)

External ingress protection IP21, 23, 40, 41, 43, 55

Space heater with hygrostat and/or thermostat

Internal lighting

100 mm or 200 mm base frame

Lifting eyes

DC Load

DC output protection (fuses or circuit breaker with contact)

Distribution board (circuit breaker with or without contact)

Communication

Modbus RS485

Remote alarm up to 8 additional relays

Special Request

Configuration

Single rectifier with no battery

Dual charger in single cabinet

Dual charger with shared battery

Battery

Batteries in charger cabinet (on shelves or drawers)

Mechanical

Other RAL painting colour

European Directives

Low voltage directive

2006/95/EC (before April 2016)

2014/35/EU (after April 2016)

EMC directive

2004/108/EC (before April 2016)

2014/30/EU (after April 2016)

Compliances

IEC/NF EN 60146-1-1: 2009

Semiconductor converters - Part 1-1: Specification of basic requirements

IEC/NF EN 61000-6-2: 2006

Electromagnetic compatibility (EMC) - Part 6-2: Generic standards - Immunity for industrial environments

IEC/NF EN 61000-6-4: 2007 AMD1: 2011

Electromagnetic compatibility (EMC) - Part 6-4: Generic standards - Emission standards for industrial environments

IEC/NF EN 61439-1: 2012

Low voltage switchgear and controlgear assemblies - Part1: General rules

IEC/NF EN 60950-1: 2013 AMD2: 2014

Information technology equipment - Safety - Part 1: General requirements

NF C58-311: 1990

Procedure for type tests for rectifier-battery charger and batteries