Chloride® FP60Z AC UPS
Industrial UPS system offering a full-IGBT innovative design. A wide range of possible options.
UPS TypeAC IEC
Ratings5 to 250 kVA
TechnologyFull IGBT
Chloride® FP60Z AC UPS
Industrial UPS system offering a full-IGBT innovative design. A wide range of possible options.
UPS TypeAC IEC
Ratings5 to 250 kVA
TechnologyFull IGBT
Market & Industry Type
Petrochemical and Chemical
Minings/Metals
Power generation plants
Oil & Gas
Water and Wastewater
Transportation (rail, metro, tramway)
Continuous manufacturing processes
Downloads
Features & Benefits
Read lessKey advantages
Safety
Bidirectional rectifier to perform battery deep discharging.
Smart access to UPS data
Large color LCD touch-pad for user interface.
USB access
Export of all the recorded events using USB flash drive.
Best-in-class performance to optimize expenses
Reduced CAPEX - Upstream transformer, switchgear and cables are downsized thanks to high input power factor, low THDi rejection and low inrush current.
Proven digital Vector Control technology to control the output waveform, even on non linear loads.
Controlled OPEX
Lower power consumption thanks to high efficiency.
Industrial-grade maintainability
Innovative design allowing an easy front access to all components.
Removable ID Cards which safeguard the UPS parameters and facilitate control board replacement.
Configurable active mimic diagram.
Industrial flexibility
Fit-for-purpose battery selection.
Galvanic isolation: either output and/or input transformers.
Wide range of electrical and mechanical options.
Technical Specification
Read lessInput
AC Voltage
3 X 400 V (380, 415) (other available on request)
Voltage Tolerance
+/- 10%
Frequency
50 Hz (60 Hz)
Frequency Tolerance
+/- 5%
Inrush current
≤ 10 x ln (other available on request)
Output
AC Voltage Single phase
1 x 230 V (220, 240) ; 1 x 110 V (115, 120) (other available on request)
AC Voltage Three phase
3 x 400 V (380, 415) ; 3 x 220 V (200, 208, 230) (other available on request)
Frequency
50 Hz (60 Hz)
Frequency stability with internal oscillator
+/- 0.05%
Frequency stability with reserve synchronism
+/- 3 % (from 1 to 5% adjustable)
Voltage stability (for 0 to 100 % load variation): Static
Voltage stability (for 0 to 100 % load variation) : Static
Voltage stability (for 0 to 100 % load variation): Dynamic
VFI SS 111 as per IEC/EN 62040-3, class 1
Inverter overload capability: 1 minute
150 % of nominal power
Inverter overload capability: 10 minutes
125 % of nominal power
Short circuit clearance (in % of nominal current): 1-ph output
250 % / 100 ms - 175 % / 5s
Short circuit clearance (in % of nominal current): 3-ph output Ph-N
315 % / 100 ms - 220 % / 5s
Short circuit clearance (in % of nominal current): 3-ph output Ph-Ph
190 % / 100 ms - 135 % / 5s
Harmonic voltage distortion: With 100% linear load
< 3%
Harmonic voltage distortion: With 100% non-linear load
SS as per IEC/EN 62040-3
Allowable power factor
0.5 lagging to 0.5 leading
Battery
Battery
Salt Metal Chloride, Lead acid or nickel cadmium, vented or recombination
Autonomy
From few minutes to several hours, on request
Battery current limitation (typical, float, & boost modes)
0.1 C (lead-acid battery) / 0.2 C (nickel-cadmium battery)
General Data
Operating temperature
0 to 40 °C (-20°...55°C on request)
Storage temperature
-20 to +70°C
Relative humidity
< 95% non condensing
Operating altitude
1000m max without derating (other available on request)
Cooling
Forced ventilation
Efficiency
Up to 90% according to rating
External protection
IP 20 according to IEC 60529 (other available on request)
Internal protection
Protection against unintentional direct contact, as per IEC 60590-1/62477-1
Cabinet colour
Grey RAL 7032 (other available on request)
Dimensions
Varying according to ratings and options
Ratings
110-120 Vdc
5 / 10 / 20 / 30 / 40 / 50 / 60 kVA
220-240 Vdc
10 / 20 / 30 / 40 / 50 / 60 / 80 / 100 / 120 / 160 / 200 / 250 / 320 / 400 / 500 kVA
400 Vdc
40 / 50 / 60 / 80 / 100 / 120 / 160 / 200 / 250 / 320 / 400 / 500 kVA
Standards
IEC62040-1:2017
Uninterruptible power systems (ups) - Part 1: Safety requirements
IEC62040-2:2016
Uninterruptible power systems (UPS) -Part 2: Electromagnetic compatibility (EMC) requirements
IEC62040-3:2011
Uninterruptible power systems (UPS) - Part 3: Method of specifying the performance and test requirements
IEC61439-1:2011
Low voltage switchgear and controlgear assemblies - Part 1: General rules
IEC60529:1989+AMD1:1999
Degrees of protection provided by enclosures (IP Code)
IEC60076-11:2004
Power transformers - Part11: Dry type transformers
Conformity
Low voltage directive
2006/95/EC and 2014/35EU
EMC directive
2004/108/EC and 2014/30/EU
CE Mark
Yes
Options
Wide range of options
Refer to datasheet in download section
FP60Z options
CP70Z offers a wide range of options